Plan Review Notes
Plan Review Notes For Permit 08050578
Permit Number 08050578
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-01 14:58:12***DENIED***
  
 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND
 STANDBY SYSTEMS TO CODES AND STANDARDS ON SHEET E0.1.
  
 2) CLEARLY IDENTIFY THE FUEL TYPE AND SHOW LOCATION OF
 FUEL SOURCE.
  
 3) IF APPLICABLE DEPENDING ON TYPE OF FUEL, SHOW
 BUILDING OPENING LOCATIONS WITH RELATION TO EXHAUST
 TERMINUS.
  
 4) PLEASE IDENTIFY WHAT BUILDING LIFE SAFETY SYSTEMS
 AND EQUIPMENT WILL BE CONNECTED TO GENERATORS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756