2008-06-16 16:10:33 | BUILDING PLAN REVIEW |
| PERMIT: 08050578 |
| ADD: 1641 WORTHINGTON RD |
| CONT: HEDRICK BROTHERS |
| TEL: (561)662-0785 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| |
| 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 / |
| CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE |
| TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING |
| TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD |
| ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS |
| ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN |
| EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF |
| RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB |
| ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE |
| SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE |
| ACCOMPLISHED AT TIME OF THE FINAL. |
| |
| 3) THERE ARE NO ARCHITECTURAL OR STRUCTURAL PLANS |
| INDICATING THE SIZE OFEQUIPMENT PADS, TYPE OF |
| COMPOSITION, AND CONNECTION FROM THE EQUIPMENT PAD TO |
| THE GENERATOR FRAME TO RESIST THE MOMENT OF |
| OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST MOMENT OF |
| OVERTURNING, UPLIFT AND SLIDING. |
| |
| 4) MISSING THE WIND DESIGN DATA: 1603.1.4 WIND DESIGN |
| DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER |
| HOUR (KM/HR). |
| 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| 3.WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS |
| AND, IF DESIGNING WITH ASCE 7, INTERNAL PRESSURE |
| COEFFICIENT. |
| 5.COMPONENTS AND CLADDING. THE DESIGN WIND |
| PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| NOT SPECIFICALLY DESIGNED BY THE |
| REGISTERED DESIGN PROFESSIONAL. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |