2 |
|
Notes |
Date |
Text |
2008-06-18 10:42:19 | 2004 FBC W/2007 REVISIONS | | REROOF | | | | DENIED BY BUILDING | | | | 1) THE ASSEMBLY THAT IS SPECIFIED ON THE NOA (PAGE 30) | | IS FOR USE AS A TILE UNDERLAYMENT. PLEASE SPECIFY THE | | APPROPRIATE ASSEMBLY FOR THE FLAT ROOF. NOTE: PAGE 26 | | IS FOR SBS ON A NON-INSULATED WOOD DECK. | | | | 2) THE ENHANCED FASTENING LETTER IS INCORRECT. ROOFING | | APPLICATION STANDARD 117 IS THE STANDARD SPECIFIED IN | | LIMITATION #7 OF THE PRODUCT APPROVAL NOA FOR | | DETERMINING THE SPACING OF THE FASTENERS AT THE | | PERIMETER AND CORNER . RAS 127 IS FOR TILE ROOFS AND | | RAS 150 IS A PRESCRIPTIVE STANDARD FOR BUR THAT WAS NOT | | ADOPTED BY THE CITY OF WEST PALM BEACH. PLEASE | | CORRECT. | | | | 3) THE FASTENER SPACING OF 3" OC CENTER FOR THE BASE | | SHEET IS INCORRECT. THE BASE SHEET FASTENERS CAN NOT BE | | ANY CLOSER THAN 4" OC PER RAS 117. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|