2008-06-18 10:42:192004 FBC W/2007 REVISIONS
 REROOF
  
 DENIED BY BUILDING
  
 1) THE ASSEMBLY THAT IS SPECIFIED ON THE NOA (PAGE 30)
 IS FOR USE AS A TILE UNDERLAYMENT. PLEASE SPECIFY THE
 APPROPRIATE ASSEMBLY FOR THE FLAT ROOF. NOTE: PAGE 26
 IS FOR SBS ON A NON-INSULATED WOOD DECK.
  
 2) THE ENHANCED FASTENING LETTER IS INCORRECT. ROOFING
 APPLICATION STANDARD 117 IS THE STANDARD SPECIFIED IN
 LIMITATION #7 OF THE PRODUCT APPROVAL NOA FOR
 DETERMINING THE SPACING OF THE FASTENERS AT THE
 PERIMETER AND CORNER . RAS 127 IS FOR TILE ROOFS AND
 RAS 150 IS A PRESCRIPTIVE STANDARD FOR BUR THAT WAS NOT
 ADOPTED BY THE CITY OF WEST PALM BEACH. PLEASE
 CORRECT.
  
 3) THE FASTENER SPACING OF 3" OC CENTER FOR THE BASE
 SHEET IS INCORRECT. THE BASE SHEET FASTENERS CAN NOT BE
 ANY CLOSER THAN 4" OC PER RAS 117. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW