Plan Review Notes
Plan Review Notes For Permit 08050554
Permit Number 08050554
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-21 10:45:48RESIDENTIAL(R3)SHUTTERS,BUILDINGREVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- REVISE INSTALLATION SCHEDULE ANCHOR SPACING.ANCHOR
 SPACING ON SHUTTERS PRODUCT APPROVAL PAGE 10 OF 14IS
 TO BE USED ONLY WHEN THE EDGE DISTANCE IS 3-1/2".
 INFORMATION GIVEN ON CITY'S INSTALLATION SCHEDULE SHOWS
 THE EDGE DISTANCE TO BE AT 3".ACCORDING TO PAGE 11 OF
 14 OFSHUTTERS DRAWINGS ANCHOR SPACING NEEDSTO BE
 REDUCED AS REQUIRED BY THE EDGE DISTANCE VERSUS SPACING
 FOR ANCHORS TABLE.REVISE ANCHOR SPACING IN CITY'S
 INSTALLATION SCHEDULE AS REQUIRED.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712