2008-06-19 15:55:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE SHEET 8.THE SHUTTER MOUNTING CONNECTION TYPE
 ON THE INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE
 NAMING CONVENTION USED ON THIS PAGE FOR WOOD SUBSTRATE
 FOR OPENINGS 11 AND 12 (FOR INSTANCE, ALTERNATIVE 1,
 THROUGH ALTERNATIVE 7).ON THE INSTALLATION SCHEDULE
 YOU HAVE SPECIFIED 12" SPACING, BUT MOST OF THE
 CONNECTION TYPES REQUIRE 6" SPACING.PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 2ND REVIEW, 12" FOR CONCRETE BLOCK SPECIFIED ON THE
 INSTALLATION SCHEDULE, BUT SEE THE PRODUCT APPROVAL.
 CONNECTION TYPE 1 REQUIRES A CONCRETE SUBSTRATE; THERE
 IS A "-' IN THE COLUMN MARKED "TO MASONRY".PLEASE
 REVISE.
  
 2-3.ADDRESSED.
  