Plan Review Notes
Plan Review Notes For Permit 08050553
Permit Number 08050553
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-11 08:48:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE SHEET 8.THE SHUTTER MOUNTING CONNECTION TYPE
 ON THE INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE
 NAMING CONVENTION USED ON THIS PAGE FOR WOOD SUBSTRATE
 FOR OPENINGS 11 AND 12 (FOR INSTANCE, ALTERNATIVE 1,
 THROUGH ALTERNATIVE 7).ON THE INSTALLATION SCHEDULE
 YOU HAVE SPECIFIED 12" SPACING, BUT MOST OF THE
 CONNECTION TYPES REQUIRE 6" SPACING.PLEASE REVISE
 INSTALLATION SCHEDULE.
  
 2.PLEASE REVISE SHUTTER MOUNTING CONNECTION TYPE FOR
 OPENING 10 TO CORRELATE WITH THE ANCHOR TYPES ON SHEET
 7 (CONNECTION TYPES 1 THROUGH 8). YOU HAVE SPECIFIED A
 CONCRETE BLOCK SUBSTRATE WITH 12" SPACING; APPEARS THAT
 6" IS REQUIRED FOR MASONRY, TYPE 2.PLEASE CLARIFY
 WHICH CONNECTION TYPE YOU ARE USING AND CONFIRM ANCHOR
 SPACING.
  
 3.PLEASE NOTE THAT THE INSTALLATION SCHEDULE IS
 REQUIRED FOR SHUTTERS ONLY (NOT WINDOWS).