Plan Review Notes For Permit 08050553 |
Permit Number |
08050553 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-06-11 08:48:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SEE SHEET 8.THE SHUTTER MOUNTING CONNECTION TYPE | | ON THE INSTALLATION SCHEDULE SHOULD CORRELATE WITH THE | | NAMING CONVENTION USED ON THIS PAGE FOR WOOD SUBSTRATE | | FOR OPENINGS 11 AND 12 (FOR INSTANCE, ALTERNATIVE 1, | | THROUGH ALTERNATIVE 7).ON THE INSTALLATION SCHEDULE | | YOU HAVE SPECIFIED 12" SPACING, BUT MOST OF THE | | CONNECTION TYPES REQUIRE 6" SPACING.PLEASE REVISE | | INSTALLATION SCHEDULE. | | | | 2.PLEASE REVISE SHUTTER MOUNTING CONNECTION TYPE FOR | | OPENING 10 TO CORRELATE WITH THE ANCHOR TYPES ON SHEET | | 7 (CONNECTION TYPES 1 THROUGH 8). YOU HAVE SPECIFIED A | | CONCRETE BLOCK SUBSTRATE WITH 12" SPACING; APPEARS THAT | | 6" IS REQUIRED FOR MASONRY, TYPE 2.PLEASE CLARIFY | | WHICH CONNECTION TYPE YOU ARE USING AND CONFIRM ANCHOR | | SPACING. | | | | 3.PLEASE NOTE THAT THE INSTALLATION SCHEDULE IS | | REQUIRED FOR SHUTTERS ONLY (NOT WINDOWS). |
|