Plan Review Notes For Permit 08050552 |
Permit Number |
08050552 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-29 10:09:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SEE SHEET 11 OF THE PRODUCT APPROVAL.AN EDGE | | DISTANCE OF 3" REQUIRES A FACTOR OF .83 APPLIED TO THE | | ANCHOR SPACING; 2" REQUIRES A .5 FACTOR.ALSO SEE | | MINIMUM SPACING. | | |
|