2008-05-29 14:19:46PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.01 DETAIL 1, EXISTING/DEMOLITION PLAN:
 INDICATES ONE LAVATORY IN DRESSING AND ONE BIDET IN THE
 MASTER BATH BEING DELETED. PLEASE ADD THE FOLLOWING TO
 NOTES PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS:
 IN THE INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A
 PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS
 REQUIRED OF PLUMBING DEMO WORK PRIOR TO COVERING DEMO
 WORK WITH FINNISH WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 2. PROVIDE A DETAIL ON HOW THE SLEEVE HOLE FOR THE
 BIDET WILL BE SAFEGUARDED AGAINST THE SPREAD OF FIRE
 AND SMOKE WHEN THE DRAINAGE PIPE IS REMOVED. PER
 FBC-2004 BUILDING SECTION 701.1 SCOPE.
  
 3. SHEET A.01 DETAIL 2, NEW FRAMING PLAN: CLEARLY
 INDICATE THE SCOPE OF WORK IN THE POWDER ROOM. DEMO
 PLAN INDICATED PLUMBING FIXTURES BEING REMOVED, HOWEVER
 THERE IS NO INDICATION IF THE OLD PLUMBING FIXTURES ARE
 BEING REINSTALLED OR IF NEW ONES ARE BEING INSTALLED.
 PLEASE CLARIFY THIS ON THE RESUBMITTAL. PER (W.P.B.AS
 AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. SHEET A.01 DETAIL 2, NEW FRAMING PLAN: CLEARLY
 INDICATE ON THE RESUBMITTED PLANS IF A NEW KITCHEN SINK
 OR THE OLD KITCHEN SINK IS BEING INSTALLED IN THE NEW
 KITCHEN COUNTER TOP. PLEASE ALSO INDICATE THE KITCHEN
 SINKS LOCATION. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHEET A.01 DETAIL 2, NEW FRAMING PLAN: CLEARLY
 INDICATE THAT THE GLASS DOOR IN THE NEW IN THE GUEST
 BATH COMPLIES WITH FBC-2004 PLUMBING SECTION 417.6
 GLAZING.WINDOWS AND DOORS WITHIN A SHOWER ENCLOSURE
 SHALL CONFORM TO THE SAFETY GLAZING REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING SECTION 2406 HAZARDOUS
 LOCATIONS.(5)
  
 6. PROVIDE A SANITARY AND POTABLE WATER ISOMETRIC
 RISER DIAGRAM OF THE PROPOSED NEW LAVATORY BEING
 INSTALLED IN THE MASTER BATHROOM. PER (W.P.B.AS
 AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(4)(6)(10)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  