2008-05-21 13:17:17PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A TITLE BLOCK FOR THE ENGINEER OF RECORD WITH
 INFORMATION IS REQUIRED ON ALL SHEETS PER
 61G15-23.002(2) FAC.
  
 2. SHEET 3 FIRST FLOOR PLAN INDICATES A 40 GAL. LOW
 BOY WATER HEATER INSTALLED IN THE CORNER UNDER A
 KITCHEN CABINET. PER FBC-2004 PLUMBING SECTION 501.4
 LOCATION. WATER HEATERS AND STORAGE TANKS SHALL BE
 LOCATED AND CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, MAINTENANCE, SERVICING AND REPLACEMENT.
 THE CODE DEFINES ACCESS AS BEING ABLE TO BE REACHED BUT
 FIRST MAY REQUIRE THE REMOVAL OF A PANEL, DOOR OR
 SIMILAR OBSTRUCTION. ACCESS TO A WATER HEATER IS NOT
 ACHIEVED IF IT IS NECESSARY TO REMOVE ANY PORTION OF
 THE STRUCTURE'S PERMANENT FINNISH MATERIALS SUCH AS THE
 CORNER OF THE CABINET. CLEARLY INDICATE HOW ACCESS TO
 THE WATER HEATER WILL BE ACHIEVED ON THE RESUBMITTAL.
 IT IS SUGGESTED THAT THE WATER HEATER BE MOVED TO THE
 A/C CLOSET WITH THE A/C PLACED ON A STAND AND THE WATER
 HEATER BE INSTALLED UNDER THE A/C UNIT.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF THE PROPOSED PLUMBING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  