Date |
Text |
2008-05-20 14:36:49 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC CHAPTER 1AS AMENDED AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1}A TITLE BLOCK FOR THE ENGINEER WITH INFORMATION PER |
| 61G15-23.002(2) FAC. IS REQUIRED. |
| |
| 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| RESIDENTIAL FLORIDA BUILDING CODE.LOCATE SAME ON |
| PLANS. |
| |
| 3}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, |
| PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS |
| PER 106.3.5.4 FBC. |
| |
| 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| |
| 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND |
| 210.52(A)(2). 2005 NEC. ALL ROOMS. |
| |
| 6} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. |
| SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| |
| 7} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN. |
| ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14,RECEPTACLE PER 210.63. |
| |
| 8} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED. |
| |
| 9} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| DWELLING.NONE IS SHOWN IN THE FRONT AND THE REAR |
| RECEPTACLE HAS A 240 VOLT DESIGNATION. |
| |
| 10} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| PROTECTED PER 210.8(A) (1).BATHS 1 & 2 DO NOT COMPLY. |
| |
| 11} INDICATE IF THE DEVICES ON THE PLAN ARE NEW OR |
| EXISTING. IF ALL NEW A NOTE WILL SUFFICE. |
| |
| 12} INDICATE THE INTENDED SCOPE OF ELECRICAL WORK. |
| |
| PROVIDE A WRITTEN RESPONSE, REMOVE OLD AND VOIDED |
| SHEETS AND PROVIDE ONE COPY OF THE OLD PLANS WHEN |
| RESUBMITTING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |