Plan Review Notes
Plan Review Notes For Permit 08050523
Permit Number 08050523
Review Stop B
Sequence Number 1
Notes
Date Text
2008-06-11 12:07:262004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) SPECIFY THE APPLICABLE BUILDING CODES AND DESIGN
 CRITERIA ON THE PLANS. SPECIFY WIND SPEED, EXPOSURE
 CATEGORY, COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOW AND DOOR OPENINGS, ETC. SEE FBC SECTION R301.
  
 3) ENGINEERS ARE REQUIRED TO LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET OF
 PLANS. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER FOR THE ENGINEERING BUSINESS ON EACH SHEET, IN
 ADDITION TO THEIR NAME AND LICENSE NUMBER. FAC
 61G15-23.002 AND FS 471
  
 4) ON SHEET 3 OF THE PLANS, ITEM #8 SPECIFIES A NEW
 FRENCH DOOR AT THE LAUNDRY ROOM. PLEASE CORRECT.
  
 5) PROVIDE ALL DIMENSIONS FOR THE NEW WOOD DECK.
 SPECIFY THE SPACING OF THE SUPPORT POSTS, JOISTS, ETC.
 SPECIFY THE ATTACHMENT OF THE DECK TO THE RESIDENCE.
 SPECIFY ALL STRAPS AND CONNECTORS. SHOW COMPLIANCE WITH
 R301.1 BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF,
 SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS,
 INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD
 LOADS AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES SHALL RESULT
 IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH CAPABLE
 OF TRANSFERRING ALL LOADS FROM THEIR POINT OF ORIGIN
 THROUGH THE LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
 VERIFY THAT THE SPECIFIED FOOTERS ARE CAPABLE OF
 RESISTING THE 140 MPH WIND SPEED. FBC 106.1.2* CITY
 AMENDMENTS
  
 6) SPECIFY THE HEIGHT OF THE DECK ABOVE GRADE. SHOW
 COMPLIANCE WITH R312.1 PORCHES, BALCONIES OR RAISED
 FLOOR SURFACES LOCATED MORE THAN 30 INCHES (762 MM)
 ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS NOT
 LESS THAN 36 INCHES (914 MM) IN HEIGHT. OPEN SIDES OF
 STAIRS WITH A TOTAL RISE OF MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR OR GRADE BELOW SHALL HAVE GUARDS
 NOT LESS THAN 34 INCHES (864 MM) IN HEIGHT MEASURED
 VERTICALLY FROM THE NOSING OF THE TREADS AND R312.2
 REQUIRED GUARDS ON OPEN SIDES OF STAIRWAYS, RAISED
 FLOOR AREAS, BALCONIES AND PORCHES SHALL HAVE
 INTERMEDIATE RAILS OR ORNAMENTAL CLOSURES WHICH DO NOT
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102MM) OR MORE IN
 DIAMETER.
  
 7) THE FOOTER DETAIL ON SHEET 5 IS REQUIRED TO COMPLY
 WITH R403.1.4 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT
 LEAST 12 INCHES (305 MM) BELOW THE UNDISTURBED GROUND
 SURFACE.
  
 8) SPECIFY THE CONNECTORS THAT WILL BE USED ON THE
 FRAMING DETAILS ON SHEET 5. SEE R301.1.
  
 9) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR FRENCH
 DOORS WITH AND WITHOUT SIDE-LITES, FIXED AND CASEMENT
 WINDOWS AS REQUIRED BY FAC RULE 9B-72.
  
 10) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 11) SPECIFY THE WINDOW TYPES AND SIZES ON THE PLANS FOR
 ALL OF THE NEW WINDOWS. FBC 106.1.1* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]