2008-06-04 14:04:07RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT,
 BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) WINDOWS AS SHOWN ON FLOOR PLAN.(REPEAT
 COMMENT).
 FLOOR PLANSHOWS 5 DOUBLE HUNG WINDOWS.PRODUCT
 APPROVAL SUBMITTED NOA 03-0701.02 IS FOR
 SIDELITE/TRANSOM WINDOW ONLY.PROVIDE 2 COPIES OF
 CORRECT PRODUCT APPROVAL.
 B) FRENCH DOORS AS SHOWN ON FLOOR PLAN.NEED 2
 COPIES. ONLY ONE WAS SUBMITTED.
  
 ***NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVALS FOR
 MULLIONS IF FLOOR PLAN DOESN'T SHOW ANY WINDOWS OR
 DOORS MULLED TOGETHER.
  
 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN
 PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN
 DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE
 TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED. (REPEAT
 COMMENT).
  
 B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE
 RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD
 BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX.
 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO
 CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 3-OWES $80.36 FOR UPDATED VALUATION AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 NOTE: ADDITIONAL RESUBMITTAL FEES WILL BE ASSESSED
 ALSO.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BYSEC. 713.13 FLORIDA STATUTE.
  