2008-06-04 14:04:07 | RESIDENTIAL (R3)DOORS AND WINDOWS REPLACEMENT, |
| BUILDING REVIEW SECOND CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- PROVIDE 2 COMPLETE COPIES OF PRODUCT APPROVALS AS |
| REQUIRED BY DCA RULE 9B-72 FOR: |
| A) WINDOWS AS SHOWN ON FLOOR PLAN.(REPEAT |
| COMMENT). |
| FLOOR PLANSHOWS 5 DOUBLE HUNG WINDOWS.PRODUCT |
| APPROVAL SUBMITTED NOA 03-0701.02 IS FOR |
| SIDELITE/TRANSOM WINDOW ONLY.PROVIDE 2 COPIES OF |
| CORRECT PRODUCT APPROVAL. |
| B) FRENCH DOORS AS SHOWN ON FLOOR PLAN.NEED 2 |
| COPIES. ONLY ONE WAS SUBMITTED. |
| |
| ***NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVALS FOR |
| MULLIONS IF FLOOR PLAN DOESN'T SHOW ANY WINDOWS OR |
| DOORS MULLED TOGETHER. |
| |
| 2- A) ENGINEER TO PROVIDE CALCULATIONS FOR DESIGN |
| PRESSURES FOR WINDOW 101.ACCORDING TO SITE PLAN |
| DRAWING. THIS WINDOW IS LOCATED ON THE END ZONE.SEE |
| TABLE R301.2(2) AND FIGURE R301.2(8) OF 2004 FLORIDA |
| RESIDENTIAL CODE AND REVISE AS REQUIRED. (REPEAT |
| COMMENT). |
| |
| B) REVISE WOOD FRAME HEADER/SILL DETAIL:NOTE |
| RELATING TO TOP HEADER BUCK SPECIFIES 1" X 3" P.T. WOOD |
| BUCK CONT. WITH 1/4" X 2-1/4"WOOD SCREWS SPACED MAX. |
| 24" O.C..WOOD SCREWS CAN'T BE USED TO ATTACH TO |
| CONCRETE BLOCK. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. (REPEAT COMMENT). |
| |
| 3-OWES $80.36 FOR UPDATED VALUATION AS REQUIRED BY |
| SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| NOTE: ADDITIONAL RESUBMITTAL FEES WILL BE ASSESSED |
| ALSO. |
| |
| 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| BYSEC. 713.13 FLORIDA STATUTE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |