Plan Review Notes For Permit 08050507 |
Permit Number |
08050507 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-24 09:35:09 | | | | | DENIED | | | | 1)PROVIDE RERECORDED NOC WITH CORRECT INFORMATION, | | THE PCN THAT WAS ON THE PERMIT APPLICATION AND ON THE | | NOC ARE INCORRECT PLEASE SEE ATTACHED PCN NUMBERS FROM | | PAPA | | | | 2)PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE | | SHUTTER SCHEDULE | | | | ACCORDIONS: | | A) SHUTTER SPANS, SHOULD ONLY HAVE ONE LENGTH | | B) PROVIDE CORRECT ORIENTATION (ACCORDIONS ARE | | INSTALLED WITH SLATS VERTICAL) | | C) PROVIDE CONNECTION TYPES FOR TOP AND BOTTOM (WALL | | MOUNT IS A1 AND FLOOR MOUNT IS B1 | | D) THE ANCHOR TYPE ON SCHEDULE IS 1/4" TAPCON BUT ZAMAC | | NAILINS ARE BEING CIRCLED ON SHEET 8 AND THEIR O/C | | SPACING IS IN THE SHUTTER SCHEDULE | | | | CLEAR PANELS: | | SAME COMMENTS AS A AND C ABOVE | | A) MIN. EDGE DISTANCE PER NOA IS 2" | | | | ALUMINUM PANELS: | | SAME COMMENTS AS A AND C | | A) MIN. EDGE DISTANCE PER ANCHOR SCHEDULE CAN BE 2" OR | | 3" | | B) SEE MIN DISTANCE FROM GLASS ON SHEET 2 IS 5 1/8" | | UNLESS SIDE ENCLOSURES ARE PROVIDED (SEE MIN ENCLOSURE | | ON SHEET 3) | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|