Plan Review Notes
Plan Review Notes For Permit 08050507
Permit Number 08050507
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-24 09:35:09 
  
 DENIED
  
 1)PROVIDE RERECORDED NOC WITH CORRECT INFORMATION,
 THE PCN THAT WAS ON THE PERMIT APPLICATION AND ON THE
 NOC ARE INCORRECT PLEASE SEE ATTACHED PCN NUMBERS FROM
 PAPA
  
 2)PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE
 SHUTTER SCHEDULE
  
 ACCORDIONS:
 A) SHUTTER SPANS, SHOULD ONLY HAVE ONE LENGTH
 B) PROVIDE CORRECT ORIENTATION (ACCORDIONS ARE
 INSTALLED WITH SLATS VERTICAL)
 C) PROVIDE CONNECTION TYPES FOR TOP AND BOTTOM (WALL
 MOUNT IS A1 AND FLOOR MOUNT IS B1
 D) THE ANCHOR TYPE ON SCHEDULE IS 1/4" TAPCON BUT ZAMAC
 NAILINS ARE BEING CIRCLED ON SHEET 8 AND THEIR O/C
 SPACING IS IN THE SHUTTER SCHEDULE
  
 CLEAR PANELS:
 SAME COMMENTS AS A AND C ABOVE
 A) MIN. EDGE DISTANCE PER NOA IS 2"
  
 ALUMINUM PANELS:
 SAME COMMENTS AS A AND C
 A) MIN. EDGE DISTANCE PER ANCHOR SCHEDULE CAN BE 2" OR
 3"
 B) SEE MIN DISTANCE FROM GLASS ON SHEET 2 IS 5 1/8"
 UNLESS SIDE ENCLOSURES ARE PROVIDED (SEE MIN ENCLOSURE
 ON SHEET 3)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved