Plan Review Notes
Plan Review Notes For Permit 08050459
Permit Number 08050459
Review Stop B
Sequence Number 2
Notes
Date Text
2008-09-08 14:48:092004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE ADDITION TO THE EXISTING HOUSE IS REQUIRED TO BE
 INSULATED, HAVE ELECTRICAL WIRING, ETC. IN ORDER TO
 COMPLY WITH CODE AND WILL BE SUBSTANTIALLY COMPLETED,
 THEREFORE, A SHELL PERMIT CAN NOT BE ISSUED FOR THIS
 PROJECT. THE VALUE OF THE PROJECT HAS BEEN ADJUSTED TO
 ACCOUNT FOR THE REDUCTION IN SQUARE FOOTAGE TO 445
 SQFT. THE VALUE HAS BEEN ADJUSTED TO $47,067.00.
 ADDITIONAL PERMIT FEES OF $ 639.00 ARE DUE. SEE FBC
 108.3* CITY AMENDMENTS. FEES MUST BE PAID BEFORE PLANS
 ARE RELEASED.
  
 3) SUBMIT 2 COPIES OF A SURVEY THAT AGREES WITH THE
 DIMENSIONS OF THE SITE PLAN ON SHEET S-1.
  
 4) THE ENERGY CALCULATION FORM IS NOT FILLED OUT
 PROPERLY. IN ORDER TO USE FORM 600C-04R THE
 PRESCRIPTIVE METHOD THE MAXIMUM GLASS TO FLOOR AREA
 ALLOWED CAN NOT EXCEED 50 PERCENT. REVISE OPENINGS OR
 USE ANOTHER METHOD TO SHOW COMPLIANCE. THERE ARE NOT
 ANY WALLS OF THE ADDITION ADJACENT TO UNCONDITIONED
 SPACE SHOWN ON THE PLANS. THE CEILING INSULATION IS
 LISTED AS R3-0 ON THE FORM AND IT SHOULD BE R30. THE
 OWNER/AGENT IS REQUIRED TO SIGN THE FORM. PLEASE
 CORRECT. SEE FBC 13-600 METHOD C.
  
 5) THE PRODUCT APPROVALS HAVE BEEN CHANGED TO LARGE
 MISSILE IMPACT WINDOWS AND DOORS. THE STORM PANEL
 INSTALLATION SCHEDULE IS NO LONGER REQUIRED. PLEASE
 REMOVE IT FROM SUBMITTALS.
  