2008-09-08 14:48:09 | 2004 FBC W/2007 REVISIONS |
| ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. |
| |
| 2) THE ADDITION TO THE EXISTING HOUSE IS REQUIRED TO BE |
| INSULATED, HAVE ELECTRICAL WIRING, ETC. IN ORDER TO |
| COMPLY WITH CODE AND WILL BE SUBSTANTIALLY COMPLETED, |
| THEREFORE, A SHELL PERMIT CAN NOT BE ISSUED FOR THIS |
| PROJECT. THE VALUE OF THE PROJECT HAS BEEN ADJUSTED TO |
| ACCOUNT FOR THE REDUCTION IN SQUARE FOOTAGE TO 445 |
| SQFT. THE VALUE HAS BEEN ADJUSTED TO $47,067.00. |
| ADDITIONAL PERMIT FEES OF $ 639.00 ARE DUE. SEE FBC |
| 108.3* CITY AMENDMENTS. FEES MUST BE PAID BEFORE PLANS |
| ARE RELEASED. |
| |
| 3) SUBMIT 2 COPIES OF A SURVEY THAT AGREES WITH THE |
| DIMENSIONS OF THE SITE PLAN ON SHEET S-1. |
| |
| 4) THE ENERGY CALCULATION FORM IS NOT FILLED OUT |
| PROPERLY. IN ORDER TO USE FORM 600C-04R THE |
| PRESCRIPTIVE METHOD THE MAXIMUM GLASS TO FLOOR AREA |
| ALLOWED CAN NOT EXCEED 50 PERCENT. REVISE OPENINGS OR |
| USE ANOTHER METHOD TO SHOW COMPLIANCE. THERE ARE NOT |
| ANY WALLS OF THE ADDITION ADJACENT TO UNCONDITIONED |
| SPACE SHOWN ON THE PLANS. THE CEILING INSULATION IS |
| LISTED AS R3-0 ON THE FORM AND IT SHOULD BE R30. THE |
| OWNER/AGENT IS REQUIRED TO SIGN THE FORM. PLEASE |
| CORRECT. SEE FBC 13-600 METHOD C. |
| |
| 5) THE PRODUCT APPROVALS HAVE BEEN CHANGED TO LARGE |
| MISSILE IMPACT WINDOWS AND DOORS. THE STORM PANEL |
| INSTALLATION SCHEDULE IS NO LONGER REQUIRED. PLEASE |
| REMOVE IT FROM SUBMITTALS. |
| |