2008-06-05 08:32:34 | 2004 FBC W/2007 REVISIONS |
| ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) THE VALUE OF THE PROJECT SPECIFIED ON THE |
| APPLICATION IS LOW. THE VALUE HAS BEEN ADJUSTED TO |
| $54,154.00. ADDITIONAL PERMIT FEES OF $ 740.87 ARE DUE. |
| SEE FBC 108.3* CITY AMENDMENTS. |
| |
| 4) SUBMIT DETAILS FOR THE ATTACHMENT OF THE EXISTING |
| FOUNDATION, WALLS AND TIE BEAM TO THE NEW ADDITION. FBC |
| 106.1.2* CITY AMENDMENTS |
| |
| 5) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION |
| REQUIRED. |
| ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| OPENINGS. R806.2 MINIMUM AREA. |
| THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA |
| MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING |
| A TRANSMISSION RATE NOT EXCEEDING 1 PERM IS INSTALLED |
| ON THE WARM SIDE OF THE CEILING. SPECIFY THE SIZE AND |
| SPACING OF SOFFIT VENTS. |
| |
| 6) THE ENERGY CALCULATION FORM IS NOT FILLED OUT |
| PROPERLY. THE INFORMATION ON FORM 600C-04R APPLIES ONLY |
| TO THE ADDITION. THE INFORMATION THAT WAS ENTERED IS |
| FOR THE WHOLE HOUSE. ALSO, THE CEILING INSULATION IS |
| SPECIFIED ON THE PLANS AS R-30 NOT R-19. PLEASE |
| CORRECT. SEE FBC 13-600 METHOD C. |
| |
| 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 8) THE PRODUCT APPROVAL NOA FOR THE FRENCH DOORS HAS |
| BEEN REVISED BY NOA 05-1116.06. PLEASE SUBMIT THE NEW |
| NOA. |
| |
| 9) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION |
| SCHEDULE INDICATING THE MOUNT TYPE, SPANS, ANCHOR TYPE |
| AND SPACING, EDGE DISTANCE, ETC. SEE ATTACHED SAMPLE |
| SCHEDULE. FBC 106.1.2* CITY AMENDMENTS |
| |