Plan Review Notes
Plan Review Notes For Permit 08050386
Permit Number 08050386
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-16 15:12:06 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1}AN ENGINEER MUST DESIGN THIS SERVICE.THE
 CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL IF
 EXEMPTIONS UNDER THOSE STATUTES ARE APPLICABLE. IN THIS
 CASE ENGINEERING IS REQUIRED BECAUSE THE SERVICE
 VOLTAGE IS OVER 240 VOLTS. 471.003--- "REQUIRES AN
 AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240 VOLTS)
 OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR 800
 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR
 INDUSTRIAL ELECTRICAL SYSTEM;".
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718