Plan Review Notes
Plan Review Notes For Permit 08050355
Permit Number 08050355
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-15 11:00:131. PANEL SCHEDULE SHOWS SINGLE POLE 30 BREAKER, BUT
 PUMP IS LISTED AS 208V WHICH REQUIRES A TWO POLE
 BREAKER.
  
 2. PANEL SCHEDULE ALSO SHOWS A SINGLE POLE 20A BREAKER
 FOR PUMP?
  
 3. NO CIRCUIT SHOWN FOR QUAD RECP. AND FOR TIME CLOCK.
  
 4. A THREE PHASE PUMP IS SHOWN BUT BREAKER IS SHON FOR
 IT.
  
 PLEASE INDICATE ON DRAWINGS THE CIRCUIT THAT FEEDS EACH
 PIECE OF EQUIPMENT. PUMPS, RELAYS TIME CLOCK, ECT ECT,
 AT THE EQUIPMENT ON PLAN
  
 THANKS
  