Plan Review Notes For Permit 08050355 |
Permit Number |
08050355 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-15 11:00:13 | 1. PANEL SCHEDULE SHOWS SINGLE POLE 30 BREAKER, BUT | | PUMP IS LISTED AS 208V WHICH REQUIRES A TWO POLE | | BREAKER. | | | | 2. PANEL SCHEDULE ALSO SHOWS A SINGLE POLE 20A BREAKER | | FOR PUMP? | | | | 3. NO CIRCUIT SHOWN FOR QUAD RECP. AND FOR TIME CLOCK. | | | | 4. A THREE PHASE PUMP IS SHOWN BUT BREAKER IS SHON FOR | | IT. | | | | PLEASE INDICATE ON DRAWINGS THE CIRCUIT THAT FEEDS EACH | | PIECE OF EQUIPMENT. PUMPS, RELAYS TIME CLOCK, ECT ECT, | | AT THE EQUIPMENT ON PLAN | | | | THANKS | | | | JAKE LEAHY644-7291 |
|