Plan Review Notes For Permit 08050263
Permit Number 08050263
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-29 15:44:36 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW WITH NO
 RESPONSE AND HAVE NOT BEEN CORRECTED. PROVIDE A WRITTEN
 RESPONSE, REMOVE OLD AND VOIDED SHEETS AND PROVIDE ONE
 COPY OF THE OLD PLANS WHEN RESUBMITTING
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED. ADJUST THE VALUE AT THE PERMIT CLERK'S DESK,
 AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PER FS 489 A LICENSED CONTRACTOR IS REQUIRED TO
 APPLY FOR THIS PERMIT. ***UNLESS THE BUILDING IS NOT
 RENTED OR SOLD FOR AT LAEST ONE YEAR AFTER CO.
  
 3} INDICATE THE MAST AND CONDUCTOR SIZES ON THE RISER
 DIAGRAM, SHEET E-1.0. 215.5 2005 NEC.
  
 4} NOTE #1, SHEET E-1.0 INCORRECTLY REVERENCES FBC 2004
 (REVISED 2003), SEE REFERENCED STANDARDS 2007
 REVUSIONS.
  
 5} THE SMOKE DETECTOR CONNECTION DETAIL (ALSO SEE THE
 DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72,
 CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES) DETAIL INDICATES
 KITCHEN OR BATH CIRCUIT FEED, SEE 210.12 FOR AFCI
 REQUIREMENTS.
  
 6} PANEL "B" HAS CIRCUITS MISLABELED AS "A".
  
 7} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE
 WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG
 RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 9} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B).
  
 10} 21.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS
 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE.
  
 NEW COMMENT:
  
 11} } THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH