| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER |
| 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| |
| 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| AMENDED. ADJUST THE VALUE AT THE PERMIT CLERK'S DESK, |
| AND PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| |
| 2} PER FS 489 A LICENSED CONTRACTOR IS REQUIRED TO |
| APPLY FOR THIS PERMIT. |
| |
| 3} INDICATE THE MAST AND CONDUCTOR SIZES ON THE RISER |
| DIAGRAM, SHEET E-1.0. 215.5 2005 NEC. |
| |
| 4} NOTE #1, SHEET E-1.0 INCORRECTLY REVERENCES FBC 2004 |
| (REVISED 2003), SEE REFERENCED STANDARDS 2007 |
| REVUSIONS. |
| |
| 5} THE SMOKE DETECTOR CONNECTION DETAIL (ALSO SEE THE |
| DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 NFPA-72, |
| CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| LOCATIONS OF THE SOUNDING DEVICES) DETAIL INDICATES |
| KITCHEN OR BATH CIRCUIT FEED, SEE 210.12 FOR AFCI |
| REQUIREMENTS. |
| |
| 6} PANEL "B" HAS CIRCUITS MISLABELED AS "A". |
| |
| 7} LOCATE AND INDICATE A DISCONNECTING MEANS FOR THE |
| WATER HEATER. SEE 422.16 NEC FOR CORD AND PLUG |
| RESTRICTIONS, AND 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| |
| 8} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14,RECEPTACLE PER 210.63. |
| |
| 9} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN |
| ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE |
| SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR |
| ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). |
| |
| 10} 21.52(C)(1) WALL COUNTER SPACES A RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT EACH WALL COUNTER SPACE THAT IS |
| 300 MM (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE |
| INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |