Date |
Text |
2008-05-15 11:15:25 | PLUMBING PLAN REVIEW: |
| DENIED **2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| COMMENTS. |
| **NOTE: THERE WAS NO RESPONSE FROM THE DESIGNER. |
| |
| 1. THE SUBMITTED IRRIGATION SYSTEM ON SHEET L-1 HAS A |
| LANDSCAPE ARCHITECT COPIED SIGNATURE AND SEAL AND IS |
| PART OF MASTER PERMIT NUMBER 05091674. PER CHAPTER 481, |
| FLORIDA STATUTES, PART LL ANY REVISIONS TO TO |
| SIGNED,SEALED AND DATED SHEETS SHALL BE BY THE ORIGINAL |
| DESIGN PROFESSIONAL OF RECORD AND HE OR SHE SHALL AFFIX |
| HIS OR HER SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA AS DEFINED IN |
| SECTION 481.303(6)(A)(B)(C)(D), FS. |
| NOTE: THE CONTRACTOR IS ALLOWED TO SUBMIT THEIR |
| ORIGINAL DESIGN PLANS AS LONG AS HE OR SHE COMPLIES |
| WITH THE FOLLOWING, ALL PLANS, SPECIFICATIONS, AND |
| ACCOMPANYING DATA BEING FILED FOR PUBLIC RECORD SHALL |
| CONTAIN THE PRINTED NAME OF THE RESPONSIBLE PERSON WITH |
| THE ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. |
| PER (W.P.B. AS AMENDED) SECTION *106.3.4.3. |
| |
| **THE RESUBMITTED PLANS DO HAVE THE LANDSCAPE |
| ARCHITECT TITLE BLOCK REMOVED, HOWEVER THEY DO NOT |
| CONTAIN THE PRINTED NAME, ORIGINAL SIGNATURE AND DATE |
| OF THE PERSON TAKING RESPONSIBILITY OF THE IRRIGATION |
| PLANS (THIS CAN BE BY THE CONTRACTOR). PER (W.P.B. AS |
| AMENDED) SECTION 106.3.4.3. |
| |
| 2. THE VALUE FOR THE IRRIGATION WORK APPEARS LOW PER |
| THE FOLLOWING, |
| FBC-2004, CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. PLEASE PROVIDE A COPY OF THE SIGNED CONTRACT |
| BY BOTH PARTIES TO VERIFY THE INDICATED VALUE ON PERMIT |
| APPLICATION OR ADJUST THE VALUE ON THE PERMIT |
| APPLICATION AND PAY THE DIFFERENCE BEFORE RESUBMITTAL. |
| |
| **NOTE: THE RESUBMITTED PLANS VALUE IS STILL LOW AND |
| THE CONTRACTOR HAS NOT PROVIDED A COPY OF THE SIGNED |
| CONTRACT BY BOTH PARTIES TO VERIFY THE INDICATED VALUE |
| ON THE PERMIT APPLICATION. PER (W.P.B. AS AMENDED) |
| SECTION 108.3. |
| |
| **THE FOLLOWING ARE NEW COMMENTS** |
| |
| 3. THE RESUBMITTED IRRIGATION PLANS ARE NOT INDICATING |
| THE LOCATION OF THE WATER SOURCE (CITY METER OR LAKE) . |
| IF THE WATER SOURCE IS CITY PLEASE PROVIDE THE LOCATION |
| OF THE REQUIRED VACUUM BREAKER OR BACKFLOW PREVENTER. |
| THESE ITEMS WERE INDICATED ON THE OLD PLANS. PER |
| FBC-2004 PLUMBING SECTION 608.16.5 CONNECTIONS TO |
| IRRIGATION SYSTEMS. |
| |
| 4. THE RESUBMITTED IRRIGATION PLANS ARE NOT INDICATING |
| THE LOCATION OF THE TIME CLOCK AND RAIN SENSOR. THESE |
| ITEMS WERE INDICATED ON THE OLD PLANS. PER WEST PALM |
| BEACH CODE- UTILTIES SECTION 90-93. RESTRICTIONS (C) |
| AND FLORIDA STATUTES, SECTION 373.62. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |