2008-06-20 18:05:02 | |
| |
| |
| DENIED |
| |
| THE FOLLOWING COMMENT WERE NOT ADDRESSED IN 1ST REVIEW |
| |
| 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| ADDED TO THE PERMIT APPLICATION FEES |
| |
| NOTE: FEES ARE DUE IN THE AMOUNT OF $851.56 FOR |
| INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| |
| 5)WINDOW TYPE #4 REQUIRES 2X4 MULLION AS STATED ON |
| SCHEDULE BUT NO PRODUCT APPROVAL WAS SUBMITTED. |
| *********THE CHANGE THAT IS REQUIRED WAS TO ADD A |
| PRODUCT APPROVAL FOR 2X4 MULLIONS TO THE SUBMITTAL , |
| PLEASE SEE THAT THE 1X4 MULLION FOR 100" OPENING WIDTH |
| AND A 108" OPENING HEIGHT WILL ONLY WORK FOR A DESIGN |
| PRESSURE OF 22 PSF OR LESS PER PAGE 5 OF THE MULLION |
| PRODUCT APPROVAL******** |
| |
| NEW COMMENTS |
| |
| 1)THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED |
| WINDOWS WERE NOT RESUBMITTED, PERMIT APPLICATION |
| PACKAGE MUST BE COMPLETE FOR FINAL STAMPING AND PERMIT |
| ISSUANCE |
| |
| 2)GLASS BLOCK PRODUCT APPROVALS ONLY MEET THE SMALL |
| MISSILE IMPACT REQUIREMENTS, OPENINGS WITHIN THE FIRST |
| 30 FEET FROM GRADE MUST MEET LARGE MISSILE IMPACT |
| CRITERIA PER 1609.1.4 FBC, THE SILICONE SET BLOCK MEETS |
| THIS REQUIREMENT OR SHUTTERS WILL BE REQUIRED AND THE |
| PRODUCT APPROVALS SUBMITTED |
| |
| 3)ONLY ONE COPY OF LANDSCAPE PLAN AND SOIL REPORT |
| WERE SUBMITTED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |