Plan Review Notes For Permit 08050091
Permit Number 08050091
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-06 11:44:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) COOLING LOAD CALCULATIONS (MANUAL J) WERE DONE ON A
 WORST CASE SCENARIO SHOWING THE GREAT ROOM EXPOSED
 WALLS FACING SOUTHWEST AND NORTHWEST, THE SURVEY SHOWS
 THE GREAT ROOM EXPOSED WALLS WILL BE FACING EAST AND
 SOUTH. COOLING LOAD CALCULATIONS MUST BE DONE TO THE
 SPECIFIC BUILDING TO BE ACCURATE. PER 2004 FBC
 13-607.1.ABC.1, PLEASE CORRECT.
  
 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 THE MECHANICAL PLAN M-1, PER 2004 WPB AMEND. 106.1.3.
  
 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]