Plan Review Notes For Permit 08050091 |
Permit Number |
08050091 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-06 11:44:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | | | 1) COOLING LOAD CALCULATIONS (MANUAL J) WERE DONE ON A | | WORST CASE SCENARIO SHOWING THE GREAT ROOM EXPOSED | | WALLS FACING SOUTHWEST AND NORTHWEST, THE SURVEY SHOWS | | THE GREAT ROOM EXPOSED WALLS WILL BE FACING EAST AND | | SOUTH. COOLING LOAD CALCULATIONS MUST BE DONE TO THE | | SPECIFIC BUILDING TO BE ACCURATE. PER 2004 FBC | | 13-607.1.ABC.1, PLEASE CORRECT. | | | | 2) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF | | THE MECHANICAL PLAN M-1, PER 2004 WPB AMEND. 106.1.3. | | | | 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON | | THEM, SEE W.P.B. AMEND. 106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|