Plan Review Notes For Permit 08050091 |
Permit Number |
08050091 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-07 11:34:39 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER | | 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE AHU CIRCUITS IN PANEL "A"ARE RATED AT 5000 W | | WITH 60 AMP OCP IN VIOLATION OF 310.16. THESE 5000W | | LOADS DO NOT CORRELATE WITH THE MANUFACTURERS | | SPECIFICATIONS ON SHEET M-1, CORRELATE SAME. | | | | 2} THE CIRCUIT (1,3) PANEL "B" FOR CONDENSER #1 @50 | | AMPS EXCEEDS THE MANUFACTURERS MAX FUSE SIZE ON SHEET | | M-1 | | | | 3} SHOW COMPLIANCE WITH THE REQUIRED A/C DISCONNECTS | | PER 440.14. SEE 110.26. | | | | 4} THERE IS A JACUZZI IN THE MASTER BATH THAT IS NOT IN | | THE PANEL SCHEDULE PER 408.4. | | | | 5} INDICATE COMPLIANCE WITH 680.43(A)(1-4) FOR | | RECEPTACLES FOR THE JACUZZI. | | | | 6} THE LOAD CALCULATION MUST REFLECT THE CHANGES FROM | | THE AHU AND JACUZZI. 220. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | 2008-05-07 09:50:49 | | | | | | | |
|