Plan Review Notes For Permit 08050054 |
Permit Number |
08050054 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-06 08:31:29 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- SHUTTERS SPAN SHOWN ON COLUMN #6 OF INSTALLATION | | SCHEDULE SUBMITTED IS THE SAME AS THE OPENING HEIGHT. | | THIS CAN'T BE SO IF THE EDGE DISTANCE ON COLUMN #8 IS | | 3-1/2". REVISE AS REQUIRED. | | | | 2- ANCHOR SPACING FOR OPENING #4 NEED TO BE REVISED | | SINCE PANEL SPAN IS OVER 8'-0" TO COMPLY WITH ITEM #1 | | ABOVE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|