Plan Review Notes
Plan Review Notes For Permit 08050054
Permit Number 08050054
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-06 08:31:29RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SHUTTERS SPAN SHOWN ON COLUMN #6 OF INSTALLATION
 SCHEDULE SUBMITTED IS THE SAME AS THE OPENING HEIGHT.
 THIS CAN'T BE SO IF THE EDGE DISTANCE ON COLUMN #8 IS
 3-1/2". REVISE AS REQUIRED.
  
 2- ANCHOR SPACING FOR OPENING #4 NEED TO BE REVISED
 SINCE PANEL SPAN IS OVER 8'-0" TO COMPLY WITH ITEM #1
 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712