2008-05-15 11:13:51 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.SEE PREVIOUS LIST, TWO SETS REQUIRED.ONLY ONE | | INSTALLATION SCHEDULE WAS PROVIDED.DUE TO WORKLOAD, | | ALL COPIES MUST BE PROVIDED BY THE CONTRACTOR. | | | | 2.SEE SHEET 11, EDGE DISTANCE CHART.AN EDGE | | DISTANCE OF 3" REQUIRES A FACTOR OF .83.PLEASE | | REVISE. | | | | 3.OPENING 7 STATES THAT THE SUBSTRATE IS BLOCK, BUT | | SPECIFIES "BOTTOM 7"."FLOOR MOUNT 7" IS HIGHLIGHTED. | | THIS REQUIRES A CONCRETE SUBSTRATE.PLEASE REVISE THE | | INSTALLATION SCHEDULE. | | |
|