Plan Review Notes For Permit 08050015 |
Permit Number |
08050015 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-05 15:47:03 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.DESIGN PRESSURES ARE TOO LOW, PLEASE SEE FBC | | R301.2.(2).PLEASE REVISE INSTALLATION SCHEDULE. | | | | 2.A 2 1/2" EDGE DISTANCE REQUIRES USING A FACTOR OF | | .75 FOR ANCHOR SPACING, SEE SHEET 8 OF THE PRODUCT | | APPROVAL.9" SPACING IS SPECIFIED ON THE INSTALLATION | | SCHEDULE; THIS IS FOR 3" EDGE DISTANCE.PLEASE | | REVISE. | | |
|