Plan Review Notes
Plan Review Notes For Permit 08050015
Permit Number 08050015
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-05 15:47:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DESIGN PRESSURES ARE TOO LOW, PLEASE SEE FBC
 R301.2.(2).PLEASE REVISE INSTALLATION SCHEDULE.
  
 2.A 2 1/2" EDGE DISTANCE REQUIRES USING A FACTOR OF
 .75 FOR ANCHOR SPACING, SEE SHEET 8 OF THE PRODUCT
 APPROVAL.9" SPACING IS SPECIFIED ON THE INSTALLATION
 SCHEDULE; THIS IS FOR 3" EDGE DISTANCE.PLEASE
 REVISE.
  