Plan Review Notes For Permit 08040848 |
Permit Number |
08040848 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-05-15 11:58:05 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | 1.RE: PREVIOUS COMMENT #3, INSTALLATION SCHEDULE, TWO | | SETS REQUIRED. PLEASE PROVIDE TWO SETS.CONTRACTORS | | ARE TO PROVIDE TWO COMPLETE COLLATED SETS OF DOCUMNTS | | FOR PERMIT ISSUANCE.ONLY ONE SET OF THE INSTALLATION | | SCHEDULE WAS PROVIDED; EACH SHEET STAPLED TO A FLOOR | | PLAN. | | | | 2.DESIGN PRESSURES HAVE NOT BEEN DECLARED ON ONE OF | | THE SHEETS; ARE YOU USING THE SAME FOR THE ENTIRE JOB? | | | | 3.SEE OPENING 9.A SPAN OF 116, DESIGN PRESSURE | | 70.6, C2/C4 SHOULD HAVE ANCHOR SPACING OF 6IN/4IN (NOT | | 10IN/6IN AS SPECIFIED) IF YOU ARE USING THE TAPCON | | CIRCLED ON THE PRODUCT APPROVAL. | | | | 4.THE LANGUAGE FOR THE ANCHORS YOU HAVE SPECIFIED ON | | THE INSTALLATION SCHEDULE DOES NOT MATCH THE | | DESCRIPTION FOR ANCHORS ON THE PRODUCT APPROVAL, SEE | | SHEET 7.PLEASE CLARIFY WHICH ANCHOR YOU ARE USING. | | | | 5.ITEMS ARE CIRCLED ON THE PRODUCT APPROVAL WHICH DO | | NOT CORRELATE WITH THE JOB.PLEASE PROVIDE INFORMATION | | SPECIFIC TO THIS JOB ONLY. | | | | PLEASE CONTACT ME IF YOU NEED ASSISTANCE. | | |
|