| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,NFPA |
| 303 2000,2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 |
| FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE |
| FOLLOWING: |
| |
| 1} THE STANDARD REFERENES ON SHEET G-2, APPLICABLE |
| CODES SECTION, SHOULD BE CHANGED TO THE ABOVE EDITIONS |
| AS THAY ARE CURRENTLY IN EFFECT. |
| |
| 2} NFPA 303 ARTICLE 3.3.1 |
| A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF |
| THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN |
| THE MARINA OR BOATYARD.INDICATE THE LOCATION OF SAME. |
| |
| 3} 555.2(3) (3) THE ELECTRICAL DATUM PLANE FOR FLOATING |
| PIERS AND LANDING STAGES THAT ARE (A) INSTALLED TO |
| PERMIT RISE AND FALL RESPONSE TO WATER LEVEL, WITHOUT |
| LATERAL MOVEMENT, AND (B) THAT ARE SO EQUIPPED THAT |
| THEY CAN RISE TO THE DATUM PLANE ESTABLISHED FOR (1) OR |
| (2), IS A HORIZONTAL PLANE 762 MM (30 IN.) ABOVE THE |
| WATER LEVEL AT THE FLOATING PIER OR LANDING STAGE AND A |
| MINIMUM OF 305 MM (12 IN.) ABOVE THE LEVEL OF THE |
| DECK. |
| 555.9 ELECTRICAL CONNECTIONS |
| ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST |
| 305 MM (12 IN.) ABOVE THE DECK OF A FLOATING PIER. ALL |
| ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST 305 MM |
| (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW |
| THE ELECTRICAL DATUM PLANE.INDICATE COMPLIANCE WITH |
| THESE ARTICLES FOR THE JUNCTION BOX AND LUMINAIRE |
| CONNECTIONS.SHEET EP1.02 HAS NO DIMENSIONS FROM THE |
| WATERLINE. |
| |
| 4} INDICATE THE CABLE DESIGNATION FOR THE "FLEX CABLE" |
| SHOWN ON SHEET EP1.02. SEE ARTICLE 555.13(A)(2)FOR TYPE |
| ALLOWED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |