Plan Review Notes
Plan Review Notes For Permit 08040841
Permit Number 08040841
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-05 17:12:35 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,NFPA
 303 2000,2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004
 FBC CHAPTER 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE STANDARD REFERENES ON SHEET G-2, APPLICABLE
 CODES SECTION, SHOULD BE CHANGED TO THE ABOVE EDITIONS
 AS THAY ARE CURRENTLY IN EFFECT.
  
 2} NFPA 303 ARTICLE 3.3.1
 A BENCH MARK INDICATING THE ELECTRICAL DATUM PLANE OF
 THE LAND AREA SHALL BE PERMANENTLY LOCATED ON SHORE IN
 THE MARINA OR BOATYARD.INDICATE THE LOCATION OF SAME.
  
 3} 555.2(3) (3) THE ELECTRICAL DATUM PLANE FOR FLOATING
 PIERS AND LANDING STAGES THAT ARE (A) INSTALLED TO
 PERMIT RISE AND FALL RESPONSE TO WATER LEVEL, WITHOUT
 LATERAL MOVEMENT, AND (B) THAT ARE SO EQUIPPED THAT
 THEY CAN RISE TO THE DATUM PLANE ESTABLISHED FOR (1) OR
 (2), IS A HORIZONTAL PLANE 762 MM (30 IN.) ABOVE THE
 WATER LEVEL AT THE FLOATING PIER OR LANDING STAGE AND A
 MINIMUM OF 305 MM (12 IN.) ABOVE THE LEVEL OF THE
 DECK.
 555.9 ELECTRICAL CONNECTIONS
 ALL ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST
 305 MM (12 IN.) ABOVE THE DECK OF A FLOATING PIER. ALL
 ELECTRICAL CONNECTIONS SHALL BE LOCATED AT LEAST 305 MM
 (12 IN.) ABOVE THE DECK OF A FIXED PIER BUT NOT BELOW
 THE ELECTRICAL DATUM PLANE.INDICATE COMPLIANCE WITH
 THESE ARTICLES FOR THE JUNCTION BOX AND LUMINAIRE
 CONNECTIONS.SHEET EP1.02 HAS NO DIMENSIONS FROM THE
 WATERLINE.
  
 4} INDICATE THE CABLE DESIGNATION FOR THE "FLEX CABLE"
 SHOWN ON SHEET EP1.02. SEE ARTICLE 555.13(A)(2)FOR TYPE
 ALLOWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718