Plan Review Notes
Plan Review Notes For Permit 08040841
Permit Number 08040841
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-08 17:12:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS; PLEASE REVISE, G2.
  
 2.G2, 60PSF DECLARED FOR GANGWAYS.PLEASE SEE FBC
 TABLE 1607.1, ASCE7.FOR ALL USES INVOLVING EXITING IN
 THE FLORIDA BUILDING CODE AND ASCE7, 100PSF IS
 REQUIRED.THE ASCE DESIGN OF MARINE FACILITES FOR THE
 BERTHING, MOORING, AND REPAIR OF VESSELS STATES: "PIERS
 LIMITED TO PEDESTRIAN USE . . . SHOULD BE DESIGNED FOR
 A MINIMUM OF 100PSF."THE FACT THAT THE TEXT GOES ON
 TO SAY THAT GANGWAYS SHOULD BE DESIGNED TO 60 - 100PSF
 IS ACKNOWLEDGED.HOWEVER, PLEASE EXPLAIN THE LOGIC OF
 THE REQUIREMENT OF 100PSF FOR THE PIER, BUT ONLY 85 (AS
 DISCUSSED) FOR THE GANGWAYS WHEN THE GANGWAYS SERVE THE
 SAME OCCUPANT LOAD AS THE PIER.THE ENGINEER WHO
 WROTE THE BOOK, JOHN GAYTHWAITE PE, STATES (VIA EMAIL)
 THAT PIERS AND GANGWAYS WITH OPEN ACCESS SHOULD BE
 DESIGNED FOR 100PSF.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS THIS MATTER
 IF THE ENGINEER FOR THE PROJECT, CH2M HILL, DOES NOT
 AGREE WITH THE 100PSF REQUIREMENT.ANY FURTHER
 DOCUMENTATION TO SUPPPORT THE DESIGNOF 85PSF PROPOSED
 WOULD BE CONSIDERED.
  
 3.FOR ALL FUTURE PERMITS, ISSUED PERMITS, AND
 SUBMITTALS RELATED TO THIS PROJECT, PLEASE HAVE THE
 ENGINEER FOR THE PROJECT, CH2M HILL, REVIEW THE PLANS
 AND SUBMITTALS PRIOR TO SUBMISSION TO THE CITY (OR, IN
 THE CASE OF THE PIER PERMIT, PROVIDE AS A SUBMITTAL TO
 AVOID PERMITTING DELAYS). THIS CAN BE DONE WITH A SHOP
 DRAWING REVIEW STAMP OR A LETTER.THIS IS REQUIRED FOR
 ALL ITEMS CURRENTLY IN PROCESS, IS A PROVISO ITEM FOR
 THE PASSED BUILDING REVIEW FOR THE PIERS.
  
 4.PLEASE CLARIFY LIVE LOAD DESIGN CRITERIA FOR THE
 FLOATING DOCKS FBC*106.3.5.1.1(8).
  
 5.DECLARE AN ANTICIPATED OCCUPANT LOAD,
 FBC*106.3.5.1.1(7).THIS STRUCTURE SERVES AS A MEANS
 OF EGRESS, BUT NO INFORMATION REGARDING ANTICIPATED USE
 WAS PROVIDED.IN DETERMINING LIVE LOAD REQUIREMENTS,
 THIS INFORMATION WOULD BE USEFUL.
  
 6.LOCATION OF GUARDS IS NOT CLEAR. PLEASE SHOW
 LOCATION AND DESIGN CRITERIA OF GUARDRAILS AND
 HANDRAILS, FBC1607, FBC1009, FBC1012, FBC11-4.8.
  
 7.THE PERMIT FOR THE PIERS STATED THAT THE RAILS AND
 GANGWAY WERE "BY OTHERS" AND THEREFORE NOT INCLUDED
 WITHIN THE SCOPE OF THAT PERMIT.THIS PERMIT
 APPLICATION STATES THAT IT IS FOR FLOATING DOCKS.DOES
 THIS INCLUDE THE GANGWAYS AND GUARD/HAND RAILS?THE
 PERMIT CAN BE ISSUED WITH SHOPS/ENGINEERING SUBMITTED
 PRIOR TO INSTALLATION.
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved