2008-05-01 13:51:58 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS. PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| *NOTE: NOT ALL CORRESPONDING LENGTHS OF CUT SECTIONS |
| OF PIPE ARE BEING INDICATED. REFERENCE THE RED CIRCLED |
| YELLOW HIGH LIGHTED AREAS INDICATING THIS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL |
| GAS SECTION 401.1 SCOPE. |
| *NOTE: THE ONLY PIPING MATERIAL BEING INDICATED IS THE |
| UNDERGROUND PE PIPE. CLEARLY INDICATE WHAT THE ABOVE |
| GROUND PIPING MATERIAL IS ON THE RESUBMITTED DRAWINGS. |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| *NOTE: THIS INCLUDES THE EXISTING BTU LOAD AS WELL AS |
| THE PROPOSED BTU LOAD. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| *NOTE: THIS INCLUDES THE EXISTING SYSTEM AS WELL AS |
| THE PROPOSED SYSTEM DISTANCE FROM THE METER. |
| |
| 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| *NOTE: THERE IS NO APPROVED GAS POOL HEATER THAT HAS |
| BEEN SUBMITTED FOR THIS POOL. PLEASE SUBMIT TWO COPIES |
| OF MANUFACTURE SHEETS FOR THE POOL HEATER CLEARLY |
| INDICATING THE MAKE, MODEL NUMBER, BTU LOAD CAPACITY |
| AND A LISTING FROM A NATIONALLY RECOGNIZED TESING |
| LABORATORY. THE FOLLOWING IS BEING INDICATED FOR THE MP |
| REGULATOR "MAXITROL 325-7L-12". PLEASE CLARIFY WHAT THE |
| 12 IS FOR ON THIS REGULATOR. PLEASE SUBMIT MANUFACTURE |
| SHEETS WITH THIS MODEL REGULATOR THAT INDICATES WHAT |
| THE 12 IS FOR. |
| |
| 6. THE VALUE ON THE PERMIT MUST BE ADJUSTED TO THE |
| FAIR MARKET VALUE (REPLACEMENT VALUE) FOR THE POOL |
| HEATER, WITH ALL MATERIALS AND LABOR. IF THE VALUE IS |
| NOT ADJUSTED THEN THE CITY WILL NEED TO ADJUST IT USING |
| THE MARSHALL & SWIFT NATIONAL VALUATION SERVICE, PER |
| 2004 WPB AMEND. 108.3. |
| |
| END OF COMMENTS: |
| |