Plan Review Notes
Plan Review Notes For Permit 08040811
Permit Number 08040811
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-02 15:04:02 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER
 1AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE AHU CIRCUITS IN PANEL "A"ARE RATED AT 5000 W
 WITH 60 AMP OCP IN VIOLATION OF 310.16. THESE 5000W
 LOADS DO NOT CORRELATE WITH THE MANUFACTURERS
 SPECIFICATIONS ON SHEET M-1, CORRELATE SAME.
  
 2} THE CIRCUIT (1,3) PANEL "B" FOR CONDENSER #1 @50
 AMPS EXCEEDS THE MANUFACTURERS MAX FUSE SIZE ON SHEET
 M-1
  
 3} THERE IS A JACUZZI IN THE MASTER BATH THAT IS NOT IN
 THE PANEL SCHEDULE PER 408.4.
  
 4} INDICATE COMPLIANCE WITH 680.43(A)(1-4) FOR
 RECEPTACLES FOR THE JACUZZI.
  
 5} THE LOAD CALCULATION MUST REFLECT THE CHANGES FROM
 THE AHU AND JACUZZI. 220.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH