2008-05-02 13:38:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW ON PLANS COMPLIANCE WITH 2004 FBC
 3003.1.4 VENTING.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE.
  
 ** IF THIS REQUIRERMENT IS EXISTING PLEASE STATE SO ON
 PLAN, IF NOT EXISTING PLEASE PROVIDE REQUIRED
 INFORMATION.
  