 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} THE FEEDERS (#1) INDICATED FOR THE 1000 AMP
 DISCONNECT "EM" ARE NOT COMPLIANT WITH 310.16, @3/0 CU.
 SAME FOR FEEDER ON THE 800 AMP BREAKER FROM THE
 GENERATOR.
  
 3} THE #10 FEEDERS ON THE SECONDARY SIDE OF TRANSFORMER
 T-18 DO NOT COMPLY WITH 310.16 AND 450.4(A), TABLE
 450.3(B)@ 125%.
  
 4} MCC-CH INDICATES IT HAS 600 AMP MAINS AND ALSO
 INDICATES MLO. CORRELATE SAME.
  
 5} PANEL EM HAS A 400 AMP BREAKER FEEDING MCC-CH, SEE
 COMMENT #4.
  
 6} INDICATE A BRANCH CIRCUIT AND PANEL DESIGNATION PER
 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
  