Plan Review Notes For Permit 08040794 |
Permit Number |
08040794 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-01 17:26:45 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | FAC. | | | | 2} THE FEEDERS (#1) INDICATED FOR THE 1000 AMP | | DISCONNECT "EM" ARE NOT COMPLIANT WITH 310.16, @3/0 CU. | | SAME FOR FEEDER ON THE 800 AMP BREAKER FROM THE | | GENERATOR. | | | | 3} THE #10 FEEDERS ON THE SECONDARY SIDE OF TRANSFORMER | | T-18 DO NOT COMPLY WITH 310.16 AND 450.4(A), TABLE | | 450.3(B)@ 125%. | | | | 4} MCC-CH INDICATES IT HAS 600 AMP MAINS AND ALSO | | INDICATES MLO. CORRELATE SAME. | | | | 5} PANEL EM HAS A 400 AMP BREAKER FEEDING MCC-CH, SEE | | COMMENT #4. | | | | 6} INDICATE A BRANCH CIRCUIT AND PANEL DESIGNATION PER | | 620.24 BRANCH CIRCUIT FOR HOISTWAY PIT LIGHTING AND | | RECEPTACLE(S). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|