Plan Review Notes For Permit 08040786 |
Permit Number |
08040786 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-01 14:07:45 | RESIDENTIAL (R3) SHUTTERS INSTALLATION, BUILDING REVIEW | | CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- ACCORDING TO KEY PLAN PROVIDED ALL THE OPENINGS ARE | | GOING TO HAVE STORM SHUTTERS.NEED TO PROVIDE AT LEAST | | ONE MEANS OF ESCAPE AS REQUIRED BY SEC. R310.4 OF 2004 | | FLORIDA RESIDENTIAL CODE. SPECIFY HOW COMPLYING WITH | | THIS CODE SECTION. | | | | 2- TAPCON SPACING FOR BOTTOM PART OF OPENING #1 NEEDS | | TO BE REDUCEDTO 5" AS REQUIREDON SHEET 7 OF 9 OF | | STORM SHUTTERS.SEE BOTTOM OF CHARTFOR SHUTTER SPAN | | BETWEEN 8'-0" AND 12'-0"WITHSECTION 6AT BOTTOM | | CONNECTION. REVISE AS REQUIRED. | | | | 3- NEED TO PROVIDE RECORDED NOTICE OF COMMENCEMENT AS | | REQUIRED BY SEC. 713.13 FLORIDA STATUTE. | | | | 4- PROVIDE 2 COPIES OF SHUTTER INSTALLATION. ONLY ONE | | PROVIDED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|