2008-05-08 10:13:04 | BUILDING PLAN REVIEW |
| PERMIT: 08040701 |
| ADD: 3810 GEORGIA AVE #101 |
| CONT: HEDRICH BROTHERS CONSTRUCTION CO. INC |
| TEL: (561)689-8808 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 3)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. STATE THE LEVEL OF ALTERATION ON THE |
| DRAWINGS. |
| |
| 4) FBC 505.2 THE DRAWINGS NEED TO INDICATE THE SQUARE |
| FOOT AREA OF THE MEZZANINE WHICH SHALL NOT EXCEED |
| ONE-THIRD OF THE AREA OF THE ROOM WHERE IT IS LOCATED. |
| |
| 5)FBC 505.1 THE HEIGHT OF CEILINGS BELOW AND ABOVE A |
| MEZZANINE SHALL NOT BE LESS THAN 7 FEET. PROVIDE AN |
| ELEVATION DRAWING OF THE FRONT VIEW OF COMPLYING WITH |
| THIS SECTION. |
| |
| 6)IF THERE IS A SPRINKLER SYSTEM INSTALLED AT THIS |
| STRUCTURE, A CEILING PLAN SHALL BE SUBMITTED SHOWING |
| THE SPRINKLER HEAD LAYOUT THROUGH OUT THE BUILDING FBC |
| 106.3.5.1.1(5) |
| |
| 7)SHEET A.1 INDICATES THAT THE EXISTING 3? 0 X 6?-8? |
| SHALL BE RELOCATED BUT THE DRAWINGS FAIL TO SHOW THE |
| OLD LOCATION OF THE DOOR. THE DRAWINGS ALSO SHOW TWO |
| DIFFERENT SIZE OF STEEL COLUMN: THE KEY LEGEND SHOWS A |
| 6 X 6 AND DETAIL 2 ON SHEET A.1 SHOWS A 4X4 COLUMN. |
| CLARIFY. |
| |
| 8)FBC TABLE 1607.1 THE MINIMUM DISTRIBUTED AND |
| CONCENTRATED LIVE LOAD FOR LIGHT STORAGE IS 125PSF NOT |
| 40PSF. THE EXISTING WOOD CEILING FLOOR JOIST IS NOT |
| ADEQUATE FOR LIGHT STORAGE PER TABLE 1607.1. SEE FBC |
| SECTION 1607 FOR MORE INFORMATION. |
| |
| 9)110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. |
| IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| PROPRIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| AN AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| SQ FT. THE |
| COMPUTATIONS & AFFIDAVIT SHALL BE FILED AS A PERMANENT |
| RECORD OF THE BLDG DEPT. |
| |
| 10)110.4.3. SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, |
| REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. |
| |
| 11)INDICATE CLEARLY THE ATTACHMENT METHOD FOR THE |
| GUARDRAIL TO THE FLOOR AND WALL SHOWING ALL FASTENERS. |
| SHOW ON THE PLANS WHERE THE NEW 4 INCH NON-BEARING WALL |
| WILL BE CONSTRUCTED. WHAT IS THE DIAGONAL PIECE SHOWN |
| BELOW THE STAIR PLATFORM? IS THIS PIECE ATTACHED TO THE |
| EXTERIOR WALL? |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |