Plan Review Notes
Plan Review Notes For Permit 08040698
Permit Number 08040698
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-14 09:48:11 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH ARTICLE 800.44(B), ABOVE
 ROOFS COMMUNICATIONS WIRES AND CABLES SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5 M (8 FT) FROM
 ALL POINTS OF ROOFS ABOVE WHICH THEY PASS.
 * THIS COMMENT WAS MADE TO FOREWARN THE CONTRACTOR THAT
 THIS COULD BE AN ISSUE. IT WILL NOW BE RESOLVED AT
 INSPECTION.
  
 2} 210.52 (A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
  
 AAMA/NPEA/NSA 2100-02 VOLUNTARY SPECIFICATIONS FOR
 SUNROOMS IN THE RESIDENTIAL BUILDING CODE REFERENCES
 R301.2.1.1.2
  
 R301.2.1.1.2 SUNROOMS.
 SUNROOMS SHALL COMPLY WITH AAMA/NPEA/NSA 2100 WITH THE
 STRUCTURAL REQUIREMENTS AND TESTING PROVISIONS OF
 CHAPTER 5 MODIFIED TO INCORPORATE ASCE 7. NOTE THE TERM
 "STRUCTURAL REQUIREMENTS". THIS ARTICLE DOES NOT
 SUPERSEDE THE 2005 NEC ARTICLE SITED ABOVE.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718