Plan Review Notes For Permit 08040698
Permit Number 08040698
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-02 16:10:58 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH ARTICLE 800.44(B), ABOVE
 ROOFS COMMUNICATIONS WIRES AND CABLES SHALL HAVE A
 VERTICAL CLEARANCE OF NOT LESS THAN 2.5 M (8 FT) FROM
 ALL POINTS OF ROOFS ABOVE WHICH THEY PASS.
  
 2} 210.52 (A) GENERAL PROVISIONS IN EVERY KITCHEN,
 FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY,
 DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM
 OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718