Plan Review Notes
Plan Review Notes For Permit 08040671
Permit Number 08040671
Review Stop B
Sequence Number 2
Notes
Date Text
2008-05-20 15:20:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.AS DISCUSSED, PROVIDE MORE INFORMATION REGARDING
 WHO WILL ACTUALLY INSTALL THE SHUTTERS.THE CONTRACT
 PROVIDED IS AN AGREEMENT TO ACT AS A LEASING AGENT; IT
 HAS NO INFORMATION REGARDING HURRICANE SHUTTER
 INSTALLATION.I ALSO STATES THAT HE MANAGES HUNDREDS
 OF PROPERTIES.IF MR. FORD MANAGES HUNDREDS OF
 PROPERTIES, HOW WILL HE GET THE SHUTTERS INSTALLED ON
 THIS BUILDING?
  
 2.SEE PREIVOUS LIST.PLEASE ADDRESS THE ISSUE OF
 WHEN THE SHUTTERS WILL BE REMOVED FROM THE BUILDNG OR,
 AS DISCUSSED, INDICATE THAT ONE WINDOW IN EACH BEDROOM
 WILL BE IMPACT RATED.
  
 3.THE PRESTORM PREPARATION PLAN MAY BE SUBMITTED VIA
 EMAIL FOR PRELIMINARY REVIEW.ONCE FINALIZED AND IF
 APPROVED BY BUILDING OFFICIAL, AN ORIGINAL SIGNED BY
 THE OWNER WILL BE REQUIRED.
  
 4.SEE THE INSTALLATION SCHEDULE.THE ITW TAPCON,
 444.2PSF, C1 CONNECTION, HOLLOW BLOCK (PAGE 5) REQUIRES
 7" ANCHOR SPACING.10" AND 5" SPECIFIED ON THE
 INSTALLATION SCHEDULE; PLEASE REVISE.
  
 THIS WAS ON S.HILL'S DESK PENDING INFORMATION FROM THE
 CONTRACTOR.THE PLANS HAVE BEEN ROUTED TO THE FRONT
 DESK PENDING APPROVAL OF THE PRESTORM PREPARATION PLAN.
 A RESUBMITTAL IS REQUIRED; INSTALLATION SCHEDULE MUST
 BE REVISED (NOT CODE COMPLIANT AS SUBMITTED).