2008-05-20 15:20:11 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.AS DISCUSSED, PROVIDE MORE INFORMATION REGARDING |
| WHO WILL ACTUALLY INSTALL THE SHUTTERS.THE CONTRACT |
| PROVIDED IS AN AGREEMENT TO ACT AS A LEASING AGENT; IT |
| HAS NO INFORMATION REGARDING HURRICANE SHUTTER |
| INSTALLATION.I ALSO STATES THAT HE MANAGES HUNDREDS |
| OF PROPERTIES.IF MR. FORD MANAGES HUNDREDS OF |
| PROPERTIES, HOW WILL HE GET THE SHUTTERS INSTALLED ON |
| THIS BUILDING? |
| |
| 2.SEE PREIVOUS LIST.PLEASE ADDRESS THE ISSUE OF |
| WHEN THE SHUTTERS WILL BE REMOVED FROM THE BUILDNG OR, |
| AS DISCUSSED, INDICATE THAT ONE WINDOW IN EACH BEDROOM |
| WILL BE IMPACT RATED. |
| |
| 3.THE PRESTORM PREPARATION PLAN MAY BE SUBMITTED VIA |
| EMAIL FOR PRELIMINARY REVIEW.ONCE FINALIZED AND IF |
| APPROVED BY BUILDING OFFICIAL, AN ORIGINAL SIGNED BY |
| THE OWNER WILL BE REQUIRED. |
| |
| 4.SEE THE INSTALLATION SCHEDULE.THE ITW TAPCON, |
| 444.2PSF, C1 CONNECTION, HOLLOW BLOCK (PAGE 5) REQUIRES |
| 7" ANCHOR SPACING.10" AND 5" SPECIFIED ON THE |
| INSTALLATION SCHEDULE; PLEASE REVISE. |
| |
| THIS WAS ON S.HILL'S DESK PENDING INFORMATION FROM THE |
| CONTRACTOR.THE PLANS HAVE BEEN ROUTED TO THE FRONT |
| DESK PENDING APPROVAL OF THE PRESTORM PREPARATION PLAN. |
| A RESUBMITTAL IS REQUIRED; INSTALLATION SCHEDULE MUST |
| BE REVISED (NOT CODE COMPLIANT AS SUBMITTED). |