2008-08-18 10:13:10 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| FROM PREVIOUS LIST: |
| |
| 1.ADDRESSED. |
| |
| 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION |
| MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE. |
| YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP |
| AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION |
| SCHEDULE FORM. |
| |
| 2ND REVIEW, PLEASE REVISE SHUTTER CONNECTION MOUNTING |
| TYPE TO CORRELATE WITH THE ANCHORS SCHEDULES.FOR THE |
| ACCORDIONS, THIS SHOULD BE C1 THROUGH C5.FOR THE |
| PANELS, WALL MOUNT 1 THROUGH 13.PLEASE NOTE THAT |
| OPENING 1 SPECIFIES TAPCONS, BUT CIRCLED ANCHOR SPACING |
| FOR SOLID SET FOR BOTTOM 8 (TAPCONS NOT PERMITTED FOR |
| THAT SPAN, SHUTTER CONNECTION MOUNTING TYPE). |
| |
| 3RD REVIEW, INSTALLATION SCHEDULE STATES WALL.THERE |
| ARE DIFFERENT TYPES OF WALL MOUNT, EACH WITH DIFFERENT |
| ANCHOR SPACING REQUIREMENTS.PLEASE REVISE AS |
| REQUESTED. |
| |
| 3.ADDRESSED. |
| |
| 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS |
| THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH, |
| DEPENDING ON TYPE OF SHUTTER. |
| |
| 2ND REVIEW, THIS WAS NOT ADDRESSED BUT AS VERTICAL WAS |
| SPECIFIED, I USED THAT DIMENSION FOR THE REVIEW. |
| |
| 3RD REVIEW, NOT ADDRESSED.PLEASE SPECIFY SPAN. |
| |