2008-06-04 15:59:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| FROM PREVIOUS LIST: |
| |
| 1.ADDRESSED. |
| |
| 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION |
| MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE. |
| YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP |
| AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION |
| SCHEDULE FORM. |
| |
| 2ND REVIEW, PLEASE REVISE SHUTTER CONNECTION MOUNTING |
| TYPE TO CORRELATE WITH THE ANCHORS SCHEDULES.FOR THE |
| ACCORDIONS, THIS SHOULD BE C1 THROUGH C5.FOR THE |
| PANELS, WALL MOUNT 1 THROUGH 13.PLEASE NOTE THAT |
| OPENING 1 SPECIFIES TAPCONS, BUT CIRCLED ANCHOR SPACING |
| FOR SOLID SET FOR BOTTOM 8 (TAPCONS NOT PERMITTED FOR |
| THAT SPAN, SHUTTER CONNECTION MOUNTING TYPE). |
| |
| 3.ADDRESSED. |
| |
| 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS |
| THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH, |
| DEPENDING ON TYPE OF SHUTTER. |
| |
| 2ND REVIEW, THIS WAS NOT ADDRESSED BUT AS VERTICAL WAS |
| SPECIFIED, I USED THAT DIMENSION FOR THE REVIEW. |
| |
| NEW COMMENTS: |
| |
| 5.1 3/4" TAPCONS SPECIFIED.THIS IS THE EMBEDMENT |
| REQUIREMENT; A LONGER TAPCON IS REQUIRED TO MEET THE |
| EMBEDMENT REQUIREMENT (STUCCO, SHUTTER TRACK). |
| |