Plan Review Notes
Plan Review Notes For Permit 08040667
Permit Number 08040667
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-28 11:55:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE COPY OF THE INSTALLATION SCHEDULE IS NOT
 COMPLETE, OPENING NUMBERS ARE CUT OFF.PLEASE PROVIDE
 A CLEAR COPY.
  
 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION
 MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE.
 YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP
 AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION
 SCHEDULE FORM.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9B72.UNSEALED ENGINEERING WAS PROVIDED WITHOUT THE
 STATE PRODUCT APPROVAL.
  
 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS
 THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH,
 DEPENDING ON TYPE OF SHUTTER.
  