Plan Review Notes For Permit 08040667 |
Permit Number |
08040667 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-28 11:55:03 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.THE COPY OF THE INSTALLATION SCHEDULE IS NOT | | COMPLETE, OPENING NUMBERS ARE CUT OFF.PLEASE PROVIDE | | A CLEAR COPY. | | | | 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION | | MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE. | | YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP | | AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION | | SCHEDULE FORM. | | | | 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | FAC9B72.UNSEALED ENGINEERING WAS PROVIDED WITHOUT THE | | STATE PRODUCT APPROVAL. | | | | 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS | | THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH, | | DEPENDING ON TYPE OF SHUTTER. | | |
|