Plan Review Notes
Plan Review Notes For Permit 08040651
Permit Number 08040651
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-29 10:03:402004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF FLOOR PLANS SPECIFYING THE
 TYPE, SIZE AND LOCATION OF THE WINDOWS BEING REPLACED.
 INDICATE ANY OPENINGS WITH MULTIPLE WINDOWS MULLED
 TOGETHER. FBC 106.1.1* CITY AMENDMENTS
  
 2) PROVIDE TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATIONS WHERE THE STUCCO WILL BE INSTALLED. FBC
 106.1.1* CITY AMENDMENTS
  
 3) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR
 THE WINDOWS, STRUCTURAL MULLIONS, AND STORM PANELS AS
 REQUIRED BY DCA RULE 9B-72. THE PRODUCT APPROVALS
 SUBMITTED FOR THE WINDOWS ARE EXPIRED.
  
 4) SUBMIT TWO COPIES OF A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 THE ANCHOR TYPE, ANCHOR SPACING, EDGE DISTANCE,
 SEPARATION DISTANCE, SPANS, ETC. SEE THE ATTACHED
 SAMPLE SCHEDULE. FBC 106.1.2* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]