Plan Review Notes For Permit 08040607 |
Permit Number |
08040607 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-28 09:16:12 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. THE IRRIGATION PERMIT APPLICATION BY CBC060458 | | ALL-SITE CONSTRUCTION INC. IS BEING DENIED BECAUSE THE | | IRRIGATION WORK IS NOT IN THE SCOPE OF THE LICENSE. PER | | F.S. 489.105(3)(B) BUILDING CONTRACTOR. PLEASE SIGN ON | | A LICENSED PLUMBING CONTRACTOR FOR THE IRRIGATION WORK | | AND TO INSTALL THE REQUIRED BACKFLOW PREVENTER IF THE | | WATER SOURCE IS CITY WATER. PER F.S. 489.105(3)(M) | | PLUMBING CONTRACTOR OR SIGN ON A LICENSED IRRIGATION | | CONTRACTOR PER F.S. 489.105(3)(Q) SPECIALTY | | CONTRACTOR. | | NOTE: IF AN IRRIGATION CONTRACTOR IS SIGNED ON TO DO | | THE IRRIGATION WORK A LICENSED PLUMBING CONTRACTOR WILL | | STILL BE REQUIRED TO INSTALL THE REQUIRED BACKFLOW | | PREVENTER IF THE WATER SOURCE IS CITY WATER AND A | | SEPERATE PERMIT WILL BE REQUIRED TO INSTALL THE | | BACKFLOW PREVENTER. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|