Plan Review Notes
Plan Review Notes For Permit 08040599
Permit Number 08040599
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-23 13:57:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS NEED THE FOLLOWING INFORMATION ON THEM.
 1) JOB ADDRESS.
 2) PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN, AND CONTRACTOR INFORMATION
 IF APPLICABLE ON THEM, PER W.P.B. AMEND. 106.1.3.
 3) EQUIPMENT SCHEDULE (WITH ALL PERTINENT
 INFORMATION).
 4) DUCT DESIGN, SUPPLY AND RETURN WITH SIZES.
 GRILL LOCATION WITH SIZES AND CFM'S.
 5) SHOW THE LOCATION OF EQUIPMENT (AHU AND
 CONDENSER UNIT).
 6) AND ANY OTHER WORK BEING DONE, PER 2004 W.P.B
 AMEND. 106.3.5.4.
  
 2) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, PER 2004 F.B.C. 106.1.1.
  