Plan Review Notes
Plan Review Notes For Permit 08040588
Permit Number 08040588
Review Stop P
Sequence Number 2
Notes
Date Text
2008-08-22 09:53:48PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE REVISED PLANS REMOVING THE GAS POOL HAVE AN
 ENGINEER'S TITLE BLOCK THAT ARE NOT SIGNED AND SEALED.
 PLEASE KNOW THAT THE ORIGINAL PLANS WERE SIGNED AND
 SEALED BYENGINEER H. JOHN GRIFFIN 2ND P. E. FLA REG.
 #38647. PLEASE KNOW THAT ANY REVISIONS TO THE PLANS
 WILL NEED TO BE SIGNED AND SEALED THE THE ORIGINAL
 DESIGN PROFESSIONAL. PER CHAPTER 471, FLORIDA STATUTES
 AND FAC 61G15-23.002.
  
 2. ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]