2008-06-20 15:07:47 | |
| |
| DENIED |
| |
| THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST |
| REVIEW |
| |
| |
| 4)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| SETBACKS |
| ********* SEE ZONING COMMENTS, SURVEY DOES MEET SIDE |
| YARD SETBACK (NOT THE SAME AS SITE PLAN USED FOR |
| DRAINAGE AND LANSCAPE)******* |
| |
| 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| *******SEE MECHANICAL COMMENTS, OVERHANG DOES NOT MEET |
| REQUIREMENTS FOR THIS PRESCRIPTIVE METHOD******* |
| |
| 13)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES |
| WITH R806.1 & 806.2 FBC RES. |
| |
| 14)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| BUILDING PER 1603.1.4 FBC PLEASE NOTE THAT THE 2006 |
| AMENDMENTS TO THE 2004 FBC REQUIRE BUILDINGS LOCATED |
| WITHIN EXP B TYPE TERRAIN THAT IS DIRECTLY ADJACENT TO |
| EXP C TYPE TERRAIN SUCH AS OPEN GOLF COURSES AND BODIES |
| OF WATER FOR A DISTANCE OF 600 FEET OR MORE IN ANY |
| QUADRANT TO BE IN AN EXP C CATEGORY. PLEASE ADJUST THE |
| DESIGN PARAMETERS AND WIND PRESSURES ACCORDINGLY |
| *******THE COMPONENT AND CLADDING TABLE ON SHEET 1 WAS |
| NOT CHANGED FOR EXPOSURE C, PLEASE INSERT CORRECT |
| DESIGN PRESSURES. THE PRODUCT APPROVALS SUBMITTED WILL |
| ALL MEET THESE INCREASED PRESSURES******** |
| |
| |
| NEW COMMENTS |
| |
| 1)PROVIDE ORIGINAL SHEET WITH IMPACT FEE STAMP OR |
| HAVE NEW DRAWINGS RE-STAMPED |
| |
| 2)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN |
| THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, |
| THE NOTICE IS VOID |
| |