| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS |
| AMENDED, CHAPTER 1ARE THE GOVERNING CODES INDICATE SAME |
| ON THE PLANS. 106.1.3 FBC AS AMENDED. |
| |
| ALL COMMENTS RELATE TO SHEET 2 OF 4, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} PROVIDE LOAD CALCULATIONS FOR THE ENTIRE SERVICE |
| INCLUDING THE ADDITION PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| |
| 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 3} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, |
| 106.3.5.4 FBC AS AMENDED. |
| |
| 4} THE NOTE ON THE RISER AND ON THE BOTTOM LEFT OF THE |
| SHEET ARE CONTRADICTORY. 200 AMPS ON THE RISER AND 150 |
| AMPS IN THE NOTE. VERIFY SERVICE RATING AND INCLUDE |
| THAT INFORMATION WITH THE PANEL SCHEDULE AND RISER |
| DIAGRAM. |
| |
| 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE ALARMS |
| ON THE PLAN. |
| |
| 6} THERE IS A SPA ON THE PLAN BUT NOT ON THE PANEL |
| SCHEDULE, NO GFI IS SHOWN ON THE SCHEDULE PER 680.43, |
| OR ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |