2008-04-28 17:31:37 | |
| |
| DENIED |
| |
| 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & 2007 |
| AMENDMENTS PER 106.1.1 FBC* |
| |
| 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| ADDED TO THE PERMIT APPLICATION FEES |
| |
| NOTE: FEES ARE DUE IN THE AMOUNT OF $370.62 FOR |
| INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| |
| 4)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| SETBACKS |
| |
| 5)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| |
| 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| |
| 7)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER |
| R313.1.1 FBC RES. |
| |
| 8)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| |
| 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| 10)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN |
| BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN |
| AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE DENIED |
| ***PLEASE NOTE THAT NEW APPROVAL WILL REQUIRE |
| ARCHITECTS REVIEW AND APPROVAL***** |
| |
| 11)NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS, |
| |
| 12)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD |
| |
| 13)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES |
| WITH R806.1 & 806.2 FBC RES. |
| |
| 14)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| BUILDING PER 1603.1.4 FBC PLEASE NOTE THAT THE 2006 |
| AMENDMENTS TO THE 2004 FBC REQUIRE BUILDINGS LOCATED |
| WITHIN EXP B TYPE TERRAIN THAT IS DIRECTLY ADJACENT TO |
| EXP C TYPE TERRAIN SUCH AS OPEN GOLF COURSES AND BODIES |
| OF WATER FOR A DISTANCE OF 600 FEET OR MORE IN ANY |
| QUADRANT TO BE IN AN EXP C CATEGORY. PLEASE ADJUST THE |
| DESIGN PARAMETERS AND WIND PRESSURES ACCORDINGLY |
| |
| 15)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT |
| |
| 16)PROVIDE DOOR AND WINDOW TYPES AND SIZES ON THE |
| DRAWINGS |
| |
| 17)THE PRODUCT APPROVALS FOR EXTERIOR DOORS HAS AN |
| INVALID STATEWIDE APPROVAL NUMBER, THE MIAMI-DADE |
| REPORT SUBMITTED IS UNDER FL # 253-R7 |
| |
| 18)THE STATEWIDE PRODUCT APPROVAL FOR ASPHALT |
| SHINGLES HAS A UL COMPLIANCE REPORT AND INSTALLATION |
| INSTRUCTIONS NOT THE MIAMI-DADE NOA THAT WAS SUBMITTED |
| WITH IT, ALSO THE MIAMI-DADE NOA HAS EXPIRED. |
| |
| 19)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER |
| R803.2.3.1 FBC RES. MIN 8D RING SHANK NAILS |
| |
| 20)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| REQUIRED PER R807.1 FBC RES. |
| |