Plan Review Notes
Plan Review Notes For Permit 08040502
Permit Number 08040502
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-26 07:41:27 
  
 DENIED
  
 1)CORRECT JOB SITE ADDRESS IS REQUIRED ON PERMIT
 APPLICATION AND IN CONSTRUCTION SERVICES DATA BASE FOR
 INSPECTIONS AND RECORDS, ADDRESS PROVIDED NOT CORRECT.
  
 2)PROVIDE LAYOUT AND SIZES OF REMAINDER OF WINDOWS IN
 BUILDING, PLEASE NOTE THAT IF REPLACEMENT OF THE GLAZED
 AREA EXCEEDS 25% OF THE TOTAL GLAZED AREA IN THE
 BUILDING OPENING PROTECTION WILL BE REQUIRED FOR THE
 NEW WINDOWS
  
 3)THE MULLION SIZE OUTLINED IN THE PRODUCT APPROVALS
 WILL WORK FOR THE VERTICAL MULLION HOWEVER WILL NOT
 MEET REQUIRED DESIGN PRESSURES FOR THE HORIZONTAL
 MULLION REQUIRED BETWEEN THE 2 SINGLE HUNG UNITS AND
 THE FIXED UNIT
  
 4)IF FIXED UNIT IS A HALF ROUND THE HEIGHT WOULD BE
 APPROX 37" NOT 30" AS STATED PLEASE CONFIRM HEIGHT,
 ALSO THE REQUIRED DESIGN PRESSURE FOR THE SQUARE
 FOOTAGE OF THESE OPENINGS IS +33.7 -36.7 PSF THE CHOSEN
 GLAZING OF THE FIXED UNIT FOR THAT SIZE DOES NOT MEET
 THIS REQUIREMENT
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561 805-6716