2008-04-29 15:58:17 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.ON THE PRODUCT APPROVAL, CIRCLE THE ANCHORING |
| METHOD AND/OR GLASS OPTION YOU PROPOSE TO USE.THIS IS |
| TO CORRELATE WITH DESIGN CRITERIA WHICH YOU HAVE |
| SPECIFIED IN YOUR DRAWING.FOR INSTANCE, DESIGN |
| CRITERIA IS -146 FOR THE OXXO 12080 SGD, BUT SHEET 1 OF |
| 23 FOR THE PRODUCT APPROVAL STATES THAT ALL DESIGN |
| PRESSURES FOR 8'0 HIGH PANELS IS -100. |
| |
| 2.THE PRODUCT APPROVAL APPEARS INCOMPLETE FOR THE |
| SLIDING GLASS DOOR.THE STATE APPROVAL REFERS TO A |
| MIAMIDADE NOA, THE SPEC SHEETS APPEAR TO BE A PART OF A |
| NOA, NO NOA COVER SHEET AND NOT ENOUGH PAGES SUBMITTED. |
| |
| |
| 3.PLEASE NOTE THAT ENGINEERING MAY BE REQUIRED |
| DEPENDING ON THE DESIGN PRESSURES USED.FBC1609.IF |
| PRODUCTS COMPLY WITH THE DESIGN PRESSURES SHOWN ON YOUR |
| DRAWING, NO ENGINEERING WILL BE RQUIRED (-138.4 TO |
| -155PSF).HOWEVER, IF YOU REDUCE YOUR DESIGN |
| PRESSURES, CERTIFICATION BY AN ENGINEER MAY BE |
| REQUIRED. |