2008-04-29 15:58:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ON THE PRODUCT APPROVAL, CIRCLE THE ANCHORING
 METHOD AND/OR GLASS OPTION YOU PROPOSE TO USE.THIS IS
 TO CORRELATE WITH DESIGN CRITERIA WHICH YOU HAVE
 SPECIFIED IN YOUR DRAWING.FOR INSTANCE, DESIGN
 CRITERIA IS -146 FOR THE OXXO 12080 SGD, BUT SHEET 1 OF
 23 FOR THE PRODUCT APPROVAL STATES THAT ALL DESIGN
 PRESSURES FOR 8'0 HIGH PANELS IS -100.
  
 2.THE PRODUCT APPROVAL APPEARS INCOMPLETE FOR THE
 SLIDING GLASS DOOR.THE STATE APPROVAL REFERS TO A
 MIAMIDADE NOA, THE SPEC SHEETS APPEAR TO BE A PART OF A
 NOA, NO NOA COVER SHEET AND NOT ENOUGH PAGES SUBMITTED.
  
  
 3.PLEASE NOTE THAT ENGINEERING MAY BE REQUIRED
 DEPENDING ON THE DESIGN PRESSURES USED.FBC1609.IF
 PRODUCTS COMPLY WITH THE DESIGN PRESSURES SHOWN ON YOUR
 DRAWING, NO ENGINEERING WILL BE RQUIRED (-138.4 TO
 -155PSF).HOWEVER, IF YOU REDUCE YOUR DESIGN
 PRESSURES, CERTIFICATION BY AN ENGINEER MAY BE
 REQUIRED.